PST2212 Additional Power Generator

Description

General

PST2212 Additional Power Generator is a Power Plant with 2.2 kW 3-phase AC Induction Motor and Field Oriented Programmable Drive for simulating a turbine with different characteristics as:

  • Steam turbine (nuclear, geothermal, fossil)
  • Hydro-electric turbine
  • Small diesel motor

The three-phase 1.2 kVA synchronous generator has electrical parameters similar to real units.

Manual or automatic control both for the frequency (=active power) and the voltage (=reactive power). One-line mimic diagrams together with power breakers and isolators and groups of digital instruments arranged in the same way as in real plants.

The PST2212-module has step-up transformer, current and voltage transformers, relay protections for generator and transformer, A and B bus bars.

Operation of breakers and isolators is controlled and

interlocked by PLC’s for safe operation by students.

The step-up transformers are operated individually and all windings can be available via terminals on the front panel.

All necessary current transformers and voltage transformers are included and the necessary windings accessable via terminals on the front panel.

Possible earthing methods:

  1. Solid earth
  2. Resistive earth
  3. Floating earth

Technical Specifications

Simulating different types of power plant units:

  • Induction Motor 2.2 kW @ 50 Hz, 2.6 kW @ 60 Hz
  • Fully programmable AC Drive with HMI for Speed/W control

Step-up Transformer:

  • Step-up Transformer 230 / 400 V, 2.0 kVA

Generator Data:

  • 4-pole Synchronous Generator, 1.2 kVA, cos phi 0.8
  • Static PWM rectifier for Voltage / VAr control
  • Voltage: 3 x 230 V
  • Nominal Current: 3.5 A
  • Frequency: 50 Hz / 60 Hz
  • Speed: 1500 rpm / 1800 rpm
  • Synchronous Reactance 97 %
  • Transient Reactance 17 %
  • Sub transient Reactance 8 %

Digital Instruments:

Multiple 3-ph Power Energy Meters displaying 32 values for U, I, P, Q, S, and cos phi is used for:

  • Generator
  • Step-up Transformer
  • Field Current
  • Rpm
  • Frequency (Set point, actual)

Included:

  • IEC61850 GOOSE device information sharing capability
  • Easy Parameter Setting Via Web Browser
  • Disturbance Recording for in-depth fault analysis

Measurements

Cubicle

WxHxD

1050x1900x1075 mm

Weight

 

245 kg

Turbine/Generator

Cubicle

WxHxD

300x560x1500 mm

Weight

 

90 kg

Power Supply

400V 3-phase, 16A. Each module connects 5 pole (L1, L2, L3, N, Earth) with CEE connection

Protection Relays

PST2212 Level 1

IED Transformer + Generator Protection (1 unit – RET630):

  • Differential Protection
  • Over/Under Voltage Protection
  • Frequency Protection (Over/Under/Gradient)
  • Negative Sequence Overcurrent Protection
  • Neutral Point Earth Fault Protection (Residual Over-Current)
  • Neutral Point Earth Fault Protection (Residual Over-Voltage)
  • HV / MV Overcurrent Protection

*1 Protection unit in total